Transformer winding losses evaluation when supplying non linear load

TitleTransformer winding losses evaluation when supplying non linear load
Publication TypeConference Paper
Year of Publication2009
AuthorsFrelin, W, Berthet L, Petit M, Vannier J-C
Conference NameProceedings of the 44th International Universities Power Engineering Conference
Date PublishedSeptember
Conference LocationUniversity of Strathclyde
KeywordsPower Quality Transformer Modelling and Sensing
Abstract

Nonlinear loads produce harmonic currents, which induce additional losses in transformers and cause temperature rise, especially in the windings. The estimation of winding eddy current loss, in the presence of harmonics, is based on the cognition of winding eddy current loss under rated conditions. This paper deals with the transformer winding loss estimation and gives a simplified winding resistance expression that takes winding eddy-current into account and permits to estimate associated losses under rated condition. The impact of transformer winding characteristics, as thickness and layer number, on the resistance variation with frequency is shown.